|本期目录/Table of Contents|

[1]李锦航,张子含,刘江峰,等.自然对流下竖直帘式中空纤维膜组件的除湿供冷特性[J].浙江理工大学学报,2023,49-50(自科一):124-130.
 LI Jinhang,ZHANG Zihan,LIU Jiangfeng,et al.Dehumidification and cooling properties of a vertical curtain  type hollow fiber membrane module under natural convection[J].Journal of Zhejiang Sci-Tech University,2023,49-50(自科一):124-130.
点击复制

自然对流下竖直帘式中空纤维膜组件的除湿供冷特性()
分享到:

浙江理工大学学报[ISSN:1673-3851/CN:33-1338/TS]

卷:
第49-50卷
期数:
2023年自科第一期
页码:
124-130
栏目:
出版日期:
2023-03-10

文章信息/Info

Title:
Dehumidification and cooling properties of a vertical curtain  type hollow fiber membrane module under natural convection
文章编号:
1673-3851 (2023) 01-0124-07
作者:
李锦航张子含刘江峰张光玉
浙江理工大学建筑工程学院,杭州 310018
Author(s):
LI Jinhang ZHANG Zihan LIU Jiangfeng ZHANG Guangyu
School of Civil Engineering and Architecture, Zhejiang Sci-Tech University, Hangzhou 310018, China
关键词:
中空纤维膜溶液除湿供冷自然对流辐射供冷
分类号:
TU831.4
文献标志码:
A
摘要:
为探讨竖直壁面在较高冷源温度下同时进行供冷除湿的可行性,开展了自然对流条件下基于中空纤维膜的竖直壁面供冷除湿特性的实验研究。利用中空纤维膜接触器技术制作了能够同时除湿供冷的组件,搭建了供冷除湿性能测试实验台,以氯化钙溶液为除湿溶液,采用正交试验方法,研究了自然对流下溶液进口质量浓度、温度、流速等参数对中空纤维膜组件除湿量、显热供冷量以及除湿效率的影响。结果表明:溶液进口质量浓度和温度对除湿量、除湿效率有重要影响,进口温度和流速对显热供冷量影响较显著。在试验因素水平取值范围内,组件单位膜面积除湿量达5~14 g/h,显热供冷量为4~24 W,除湿效率为28%~65%,表明该组件具有一定的工程应用前景。

参考文献/References:

1Fang S, Zhi X Q, Cheng X W, et al. Numerical study on the moisture transfer characteristics of membrane - based liquid desiccant dehumidifiers: resistance distribution and concentration polarization J. International Journal of Heat and Mass Transfer, 2020, 155: 119877.

2Zhang L Z, Huang S M, Pei L X. Conjugate heat and mass transfer in a cross-flow hollow fiber membrane contactor for liquid desiccant air dehumidificationJ. International Journal of Heat and Mass Transfer, 2012, 55(25/26): 8061-8072.

3Li G P, Zhang L Z. Investigation of a solar energy driven and hollow fiber membrane-based humidification-dehumidification desalination systemJ. Applied Energy, 2016, 177: 393-408.

4]曾瑞璇,颜承初,李梅. 除湿等级划分及深度除湿技术研究进展[J. 制冷学报, 2020, 41(6):12-21.

5Zhang N, Yin S Y, Yang H H. Transient performance of coupled heat and mass transfer in cross-flow hollow fiber membrane module for air dehumidificationJ. International Journal of Refrigeration, 2019, 108: 190-199.

6]张光玉. 一种空间热湿环境控制装置: CN107166568AP. 2018-02-23.

7]姚颖, 张光玉. 基于TRIZ的辐射供冷表面凝露防控技术研究[J. 制冷与空调, 2018, 18(11): 19-22.

8Huang S M, Yang M L. Heat and mass transfer enhancement in a cross-flow elliptical hollow fiber membrane contactor used for liquid desiccant air dehumidificationJ. Journal of Membrane Science, 2014, 449:184-192.

9]张宁, 张立志. 基于质量积耗散的膜法除湿组件结构设计[J. 工程热物理学报, 2014, 35(10): 2023-2026.

10]梅宁, 何思远, 赵健, . 中空纤维膜管内LiBr溶液除湿过程的数值研究[J. 热科学与技术, 2015, 14(5): 362-369.

undefined

备注/Memo

备注/Memo:
收稿日期: 2022-02-25
网络出版日期:2022-06-01
基金项目: 浙江省自然科学基金项目(LY22E060004)
作者简介: 李锦航(1997-),男,浙江台州人,硕士研究生,主要从事暖通空调新技术方面的研究
通信作者: 张光玉,E-mail:guangyuzhang@zstu.edu.cn
更新日期/Last Update: 2023-04-03