[1]杨艺真,马景辉,戴博斌,等.冷热工况下混凝土辐射地板的蓄释热性能分析[J].浙江理工大学学报,2021,45-46(自科一):117-125.
 YANG Yizhen,MA Jinghui,DAI Bobin,et al.Thermal storage and release characteristics of concrete radiant floor under cooling and heating conditions[J].Journal of Zhejiang Sci-Tech University,2021,45-46(自科一):117-125.
点击复制

冷热工况下混凝土辐射地板的蓄释热性能分析()
分享到:

浙江理工大学学报[ISSN:1673-3851/CN:33-1338/TS]

卷:
第45-46卷
期数:
2021年自科第一期
页码:
117-125
栏目:
出版日期:
2021-01-16

文章信息/Info

Title:
Thermal storage and release characteristics of concrete radiant floor under cooling and heating conditions
文章编号:
1673-3851 (2021) 01-0117-09
作者:
杨艺真马景辉戴博斌魏厚福
浙江理工大学建筑工程学院,杭州 310018
Author(s):
YANG Yizhen MA Jinghui DAI Bobin WEI Houfu
School of Civil Engineering and Architecture, Zhejiang Sci-Tech University, Hangzhou 310018, China
关键词:
混凝土辐射地板供冷工况供暖工况时间常数蓄释热性能
分类号:
TU832 1+6
文献标志码:
A
摘要:
为了阐明混凝土辐射地板的蓄释热性能,从时间常数的角度出发,通过实验分析混凝土辐射地板在蓄热、释热过程中温度及热量的响应特征。结果表明:供暖工况的时间常数快于供冷工况,混凝土辐射地板温度更易趋于稳定。当供水流量为6 L/min、1倍时间常数时,在环境温度(260±10) ℃、供水温度221 ℃的供冷工况下,120 mm厚辐射地板试块的平均蓄冷能力和释冷能力分别为216 W/m2和117 W/m2;在环境温度(165±10) ℃、供水温度298 ℃的供暖工况下,辐射地板试块的平均蓄热和释热能力则分别为837 W/m2和402 W/m2。供水流量对混凝土辐射地板的蓄释热能力影响较小,但通过改变供水温度能够明显提高混凝土辐射地板的蓄释热能力以及变化速率。随着供水温度和罩内空气温度之差的增大,累计蓄热量呈指数关系上升,累计释热量则呈线性关系上升。该研究结果可为混凝土辐射系统的设计、运行控制策略的制定提供依据。

参考文献/References:

[1] Kang Z Q, Peng X Y, Cheng X C, et al. Analysis of condensation and thermal comfort of two kinds of compound radiant cooling air conditioning systems based on displacement ventilation[J]. Procedia Engineering, 2017, 205: 1529-1534.
[2] Ma J H, Gao Y. Study on the radiant cooling system with water flow rate on roof[C]//2010 International Conference on Mechanic Automation and Control Engineering, Wuhan. IEEE, 2010: 1940-1943.
[3] Carnieletto L, Kazanci O B, Carli M D, et al. Why couple renewable energy sources with radiant systems: Current trends, limitations and potential[C]//Roomvent & Ventilation 2018. Espoo: Aalto University, 2018: 965-970.
[4] Rhee K N, Olesen B W, Kim K W. Ten questions about radiant heating and cooling systems[J]. Building and Environment, 2017, 112: 367-381.
[5] 李娜, 裴智超, 王永红,等. 天棚辐射混凝土板显热蓄能特性研究[J]. 建筑节能, 2011, 39(3): 48-51.
[6] Lehmann B, Dorer V, Gwerder M, et al. Thermally activated building systems (TABS): Energy efficiency as a function of control strategy, hydronic circuit topology and (cold) generation system[J]. Applied Energy, 2011, 88(1): 180-191.
[7] Park S H, Chung W J, Yeo M S, et al. Evaluation of the thermal performance of a Thermally Activated Building System (TABS) according to the thermal load in a residential building[J]. Energy and Buildings, 2014, 73: 69-82.
[8] Zhang X H, Li N P, Su L, et al. Experimental study on the characteristics of nonsteady state radiation heat transfer in the room with concrete ceiling radiant cooling panels[J]. Building and Environment, 2016, 96: 157-169.
[9] Tahersima M, Tikalsky P. Experimental and numerical study on heating performance of the mass and thin concrete radiant floors with ground source systems[J]. Construction and Building Materials, 2018, 178: 360-371.
[10]Tahersima M, Tikalsky P, Revankar R. An experimental study on using a mass radiant floor with geothermal system as thermal battery of the building[J]. Building and Environment, 2018, 133: 8-18.

备注/Memo

备注/Memo:
收稿日期:2020-06-24
网络出版日期: 2020-08-07
基金项目:浙江省基础公益研究计划项目(LGG19E080003)
作者简介:杨艺真(1995-),女,浙江杭州人,硕士研究生,主要从事辐射冷暖房、被动式建筑设计方面的研究